The table below includes a list of error codes for the 1000W & 2000W Inverters (Non-transfer models), the conditions that trigger them, and the corrective actions you can take to clear the code:
Code | Condition | Corrective Action |
E01 | Unit has sensed input under voltage and has shutdown | Recharge battery immediately and restart unit |
E02 | Unit has sensed input over voltage and has shutdown | Check battery voltage or if any external charger is connected to the battery bank |
E03 | Unit output has sensed overload or short circuit and has shutdown | Check load connected to the output. Reduce load and restart the unit |
E04 | Unit has sensed internal temperature was high and has shutdown | Turn unit off and wait for 15 minutes before restarting. Check if any object has blocked the air flow of the unit |
E05 | Unit has sensed input voltage is low and warning occurs | Recharge battery as unit will shutdown shortly |
E06 | Unit has sensed load connected is close to overload shutdown limit | Reduce load |
E07 | Unit has sensed internal temperature is high and is lose to thermal shutdown limit | Reduce load and check if any ventilation of the unit is blocked. |