To program the settings on your Transfer Inverter, take the following steps
- Press and hold the "SELECT" and "POWER" buttons together for around 5 seconds
- The remote will display "PS". Press "SELECT" to cycle through the different inverter settings. Press and hold "SELECT" to confirm the inverter setting. See the table below for setting descriptions:
Inverter Settings PS0 Inverter is disabled. AC Output is getting the power from utility (AC Input) only. When utility power is not available, the unit will not provide AC backup function from the inverter, the display automatically turns off in approximately 10 seconds
When the "POWER" button is pressed again, the display will turn on for another 10 seconds
To enable the inverter or turn on the backup function, this PS0 settings has to changed to another different setting.
PS1 Inverter is set to standby mode with power save (load sense) mode OFF. Unit will provide AC backup function when utility power is NOT available. PS2 Inverter is set to standby mode with power save (load sense) mode ON. Unit will provide continuous AC backup function only when utility power is NOT available AND the load connected to the output is >10W.
Once it is on, the unit will automatically return to power save (load sense) mode when the connected AC load drops < 3@
Note: During power save mode, the inverter will turn on every few seconds for a few AC cycles to check on the > 10W power consumption
PS4 Same function as PS1 and the "POWER" button can be used to turn the AC Output ON and OFF, even with the AC input power being present in By-Pass mode.
When the unit is turned off using the "POWER" button, the display remains ON showing the batter voltage and the "Status" LED turns off.
PS6 *Recommended Setting*
AC Transfer Switch is active with the inverter switched ON or OFF
If the inverter is switched off, with AC input present, the inverter will pass the AC through to the inverter output side. If the AC input is removed, the inverter will stay in the off position.
If the inverter is switched on with AC input present, the inverter will pass the AC through to the inverter output side. If the AC input is removed, the inverter will stay in the on position supplying the inverter output side from the battery input.
To understand if the inverter is turned ON or OFF when AC input is present:
Inverter on - Display ON
Inverter off - Display OFF
- The remote will display "AL". Press "SELECT" to cycle the alarm on and off. Press and hold "SELECT" to confirm the alarm setting. The alarm settings are as follows
Alarm Setting AL0 Fault and warning audible alarm is disabled. The display panel only shows error code and the audible alarm will not sound AL1 Audible Alarm will sound when fault or warning occurs - The remote will display "Sd". Press "SELECT" to cycle through the Battery Under Voltage Settings. Press and hold "SELECT" to confirm the voltage setting you have chosen. The voltage settings are as follows:
Battery Under Voltage Setting SdL Battery under Voltage is set to LOW
Under voltage alarm: 11Vdc
Under voltage alarm recovery 11.3Vdc
Under voltage shutdown 10.5Vdc
Under Voltage shutdown recovery 12.0Vdc
SdH Battery under Voltage is set to HIGH
Under voltage alarm: 12.1Vdc
Under voltage alarm recovery 12.3Vdc
Under voltage shutdown 11.8Vdc
Under Voltage shutdown recovery 12.6Vdc
- The remote will display "Fd". If you wish to perform a factory reset, press and hold "SELECT". The factory settings are as PS1, AL1, and SdL.
- The remote will exit the settings menu automatically if "POWER" or "SELECT" are not pressed within 5 seconds.
For information on how to program the settings on your transfer inverter, check out our inverter video series here.